Specifications
Generator Specifications
10 kW
Rated Maximum Load Current* (at 25°C/77°F, LP)*:
at 240 Volts ....................................................................41.7 Amps
Rated AC Voltage .....................................................120/240 Volts
Phase ................................................................................ Single phase
Rated Frequency ................................................................. 60 Hertz
Generator Breaker ................................................................50 Amp
Normal Operating Range .. -20°F (-28.8°C) to 104°F (40°C)
Output Sound Level 72.3 dB(A) at 23 ft. (7 m) at normal load
Shipping Weight ...................................................... 330 lb (149 kg)
* Natural gas rating will depend on specific fuel but typical derates are between 10 to
20% off the LP gas rating.
Engine Specifications
Displacement ..............................................................35 ci. (570 cc)
Bore ......................................................................... 2.83 in. (71.9 mm)
Stroke ..................................................................... 2.76 in. (70.1 mm)
Spark Plug Gap ............................................... 0.020 in. (0.51 mm)
Spark Plug Torque ............................................180 lb-in. (20 Nm)
Armature Air Gap .............0.005 - 0.008 in. (0.13 - 0.20 mm)
Intake Valve Clearance ..0.004 - 0.006 in. (0.10 - 0.15 mm)
Exhaust Valve Clearance 0.004 - 0.006 in. (0.10 - 0.15 mm)
Oil Type ......................................................................5W30 Synthetic
Oil Capacity (
including oil filter
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) to CSA (Canadian Standards Association) standard
C22.2 No. 100-4 (motors and generators).
36
) ...........42 - 45 oz. (1.24 - 1.33 L)
8 kW
Rated Maximum Load Current* (at 25°C/77°F, LP)*:
at 240 Volts ....................................................................33.3 Amps
Rated AC Voltage .....................................................120/240 Volts
Phase ................................................................................ Single phase
Rated Frequency ................................................................. 60 Hertz
Generator Breaker ................................................................35 Amp
Normal Operating Range .. -20°F (-28.8°C) to 104°F (40°C)
Output Sound Level 76.8 dB(A) at 23 ft. (7 m) at normal load
Shipping Weight ...................................................... 340 lb (154 kg)
* Natural gas rating will depend on specific fuel but typical derates are between 10 to
20% off the LP gas rating.
Displacement ..............................................................31 ci. (500 cc)
Bore ......................................................................... 3.56 in. (90.4 mm)
Stroke ..................................................................... 3.06 in. (77.7 mm)
Spark Plug Gap ............................................... 0.020 in. (0.51 mm)
Spark Plug Torque ............................................180 lb-in. (20 Nm)
Armature Air Gap .............0.005 - 0.008 in. (0.13 - 0.20 mm)
Intake Valve Clearance ..0.004 - 0.006 in. (0.10 - 0.15 mm)
Exhaust Valve Clearance 0.004 - 0.006 in. (0.10 - 0.15 mm)
Oil Type ......................................................................5W30 Synthetic
Oil Capacity (
) ...............................................48 oz. (1.42 L)
with filter