Quick Parameter Reference, Faults and Alarms
Fault/Alarm
A0762:
It indicates to the user that the Main
High Level for Main
PID controller feedback is high.
PID Controller
Feedback
F0763:
It indicates to the user that the Main
High Level for Main
PID controller feedback is high.
PID Controller
Feedback
A0764:
It indicates to the user that the
CFW701 in Sleep
CFW701 frequency inverter is in
Mode
Sleep mode.
A0766:
It indicates to the user that the dry
Dry Pump Detected
pump condition was detected for the
pump driven by CFW701 frequency
inverter.
F0767:
It indicates to the user that the dry
Dry Pump Detected
pump condition was detected for the
pump driven by CFW701 frequency
inverter.
A0768:
It indicates to the user that the
Broken Belt
broken belt condition was detected
Detected
for the motor driven by CFW701
frequency inverter.
F0769:
It indicates to the user that the
Broken Belt
broken belt condition was detected
Detected
for the motor driven by CFW701
frequency inverter.
A0770:
It indicates to the user that the need
Filter Maintenance
to change the filter system.
F0771:
It indicates to the user that the need
Filter Maintenance
to change the filter system.
A0780:
It indicates to the user there is
Programming
not analog input programmed for
AIx for External
External PID controller 1 feedback.
PID Controller 1
Feedback
A0782:
It indicates to the user there is not
Programming
digital input programmed for External
DIx for External
PID controller 1 Automatic/Manual
PID Controller 1
selection.
Automatic/Manual
Selection
A0784:
It indicates to the user there is not
Programming AOx
analog output programmed for
for External PID
External PID controller 1 output.
Controller 1 Output
A0786:
It indicates to the user that the
Low Level for External
External PID controller 1 feedback
PID Controller 1
is low.
Feedback
F0787:
It indicates to the user that the
Low Level for External
External PID controller 1 feedback
PID Controller 1
is low.
Feedback
26 | CFW701
Description
Parameter P1030 is programmed in 1 and the Main
PID controller feedback value is remaining above the
value programmed in P1033 for the time programmed
in P1034.
Parameter P1030 is programmed in 2 and the Main
PID controller feedback value is remaining above the
value programmed in P1033 for the time programmed
in P1034.
Main PID controller is enabled and in Automatic mode
and the motor speed is remaining below the speed
value programmed in P1036 for the time programmed
in P1037.
Parameter P1042 is programmed in 1 and the pump
driven by CFW701 frequency inverter is running faster
than speed programmed in P1043 and the motor torque
is remaining below the torque value programmed in
P1044 for the time programmed in P1045.
Parameter P1042 is programmed in 2 and the pump
driven by CFW701 frequency inverter is running faster
than speed programmed in P1043 and the motor torque
is remaining below the torque value programmed in
P1044 for the time programmed in P1045.
Parameter P1046 is programmed in 1 and the motor
driven by CFW701 frequency inverter is running faster
than speed programmed in P1047 and the motor torque
is remaining below the torque value programmed in
P1048 for the time programmed in P1049.
Parameter P1046 is programmed in 2 and the motor
driven by CFW701 frequency inverter is running faster
than speed programmed in P1047 and the motor torque
is remaining below the torque value programmed in
P1048 for the time programmed in P1049.
Parameter P1050 is programmed in 1 and the operation
time of motor driven by CFW701 frequency inverter
displayed in P1052 is greater than the time programmed
in P1051.
Parameter P1050 is programmed in 2 and the operation
time of motor driven by CFW701 frequency inverter
displayed in P1052 is greater than the time programmed
in P1051.
Parameter P0231 or P0236 or P0241 is not
programmed in 8.
Parameter P0263 or P0264 or P0265 or P0266
or P0267 or P0268 or P0269 or P0270 is not
programmed in 21.
Parameter P0251 or P0254 is not programmed in 16.
Parameter P1075 is programmed in 1 and the External
PID controller 1 feedback value is remaining below the
value programmed in P1076 for the time programmed
in P1077.
Parameter P1075 is programmed in 2 and the External
PID controller 1 Feedback value is remaining below the
value programmed in P1076 for the time programmed
in P1077.
Possible Causes