WEG CFW701 Referencia Rápida página 11

Ocultar thumbs Ver también para CFW701:
Idiomas disponibles

Idiomas disponibles

Quick Parameter Reference, Faults and Alarms
Param.
Function
P0251
AO1 Function
P0252
AO1 Gain
P0253
AO1 Signal Type
P0254
AO2 Function
P0255
AO2 Gain
P0256
AO2 Signal Type
P0263
DI1 Function
P0264
DI2 Function
P0265
DI3 Function
P0266
DI4 Function
P0267
DI5 Function
P0268
DI6 Function
P0269
DI7 Function
P0270
DI8 Function
10 | CFW701
Adjustable
Range
0 = Speed Ref.
1 = Total Ref.
2 = Real Speed
3 = Torque Cur. Ref
4 = Torque Current
5 = Output Current
6 = Active Current
7 = Output Power
8 = Torque Cur. > 0
9 = Motor Torque
10 = SoftPLC
11 = PTC
12 = Motor Ixt
13 = P0696 Value
14 = P0697 Value
15 = Id* Current
16 = External PID 1 Output
17 = External PID 2 Output
0.000 to 9.999
0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
See options in P0251
0.000 to 9.999
See options in P0253
0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Fast Stop
4 = FWD/REV
5 = LOC/REM
6 = JOG
7 = SoftPLC
8 = Ramp 2
9 = Speed/Torque
10 = JOG+
11 = JOG-
12 = No Ext. Alarm
13 = No Ext. Fault
14 = Reset
15 = Disab.FlyStart
16 = DC Link Regul.
17 = Progr. Off
18 = Load User 1
19 = Load User 2
20 = Main PID Aut/Man
21 = External PID 1 Aut/Man
22 = External PID 2 Aut/Man
23 = Bypass Mode
24 = Fire Mode
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
Factory
User
Propr.
Setting
Setting
16
1.000
0
cfg
17
1.000
0
cfg
1
cfg
4
cfg
0
cfg
20
cfg
21
cfg
22
cfg
0
cfg
0
cfg
Groups
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O