Rack mounting

Figure 4 shows how to install the STS
module in a 19-inch bay using the four
M6 bolts and the cage nuts positioned
at the desired height in the cabinet
uprights.
The module is not as wide as the bay
and therefore does not obstruct the flow
of air.
If the temperature inside the
bay can rise above 35 °C,
ventilation is required. If this is
not possible, the STS module
should be installed outside the
bay.
On a flat surface
Figure 5 shows how to attach the
adhesive footpads under the STS module
for installation on a flat surface.
Page 8 - 51027617EN/AI
Fig. 4
Fig. 5