Contents
1.
...................................................................................
2
5.
Drainage piping work ...............................................................................
6
2.
location ..................................................................................
3
6.
Electrical work ..........................................................................................
7
3.
the indoor unit ...........................................................................
3
7. Test run ..................................................................................................
12
4.
5
8.
function (Option) ......................................................
15
1. Safety precautions
Before
installing
the unit, make
sure you read all the "Safety
precau-
tions".
Please report to your
supply authority
or obtain their
consent
before
connecting
this equipment
to the power suppmy system.
Warning:
Describes
precautions
that must be observed
to prevent
danger of injury or
death to the user.
Z_ Caution:
Describes
precautions
that must be observed
to prevent damage to the unit.
After installation
work has been completed, explain the "Safety precautions;'
use, and
maintenance
of the unit to the customer
according to the information in the Operation
Manual and perform the test run to ensure
normal operation.
Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent
users.
(_:
Indicates
which must be
a
part
grounded.
Warning:
Carefully
read the labels affixed
to the main unit.
Warning:
,, Ask a dealer or an authorized
technician
to install the unit.
,, For installation work, follow the instructions
in the Installation
Manual and use
tools and pipe components
specifically
made for use with refrigerant specified
in the outdoor
unit installation
manual
, The unit must be installed according
to the instructions
in order to minimize
the risk of damage
from earthquakes,
typhoons,
or strong winds.
An incor-
rectly installed unit may fall down and cause damage
or injuries.
,, The unit must be securely installed on a structure
that can sustain its weight.
,, if the air conditioner
is installed
in a small room, measures
must be taken to
prevent the refrigerant
concentration
in the room from exceeding
the safety
limit in the event of refrigerant leakage. Should the refrigerant
leak and cause
the concentration
limit to be exceeded,
hazards due to lack of oxygen in the
room may result.
o Ventilate the room if refrigerant
leaks during operation,
if refrigerant
comes
into contact
with a flame, poisonous
gases will be released.
, All electric work
must be performed
by a qualified
technician
according
to
local regulations
and the instructions
given
in this manual.
, Use only specified
cables
for wiring.
, The terminal
block cover
panel of the unit must be firmly
attached.
o Use only accessories
authorized
by Mitsubishi
Electric
and ask a dealer
or
an authorized
technician
to instamm them.
, The user shoumd never attempt to repair the unit or transfer
it to another
moca-
tion.
o After installation
has been completed,
check for refrigerant
leaks, if refriger-
ant leaks into the room and comes
into contact
with the flame of a heater or
portabme cooking
range, poisonous
gases will be released.
1.1. Before installation (Environment)
Caution:
,, Do not use the unit in an unusuam environment,
if the air conditioner
is in-
stalmedin areas exposed
to steam, vomatimeoim(incmuding machine
oim),or sulfuric
gas, areas exposed to high salt content
such as the seaside, the performance
can be significantmy reduced and the internam parts can be damaged.
,, Do not install the unit where combustible
gases may leak, be produced, flow,
or accumulate.
If combustible
gas accumulates
around
the unit, fire or explo-
sion may resumt.
,, Do not keep food, plants, caged pets, artwork,
or precision
instruments
in the
direct airflow
of the indoor unit or too close to the unit as these
items can be
damaged
by temperature
changes
or dripping water.
o When the room humidity exceeds 80% or when the drainpipe is cmogged, wa-
ter may drip from the indoor unit. Do not install the indoor unit where such
dripping
can cause damage.
, When installing the unit in a hospital or communications
office,
be prepared
for noise and electronic
interference.
Inverters, home appliances,
high-fre-
quency medical
equipment,
and radio communications
equipment
can cause
the air conditioner
to malfunction
or breakdown.The
air conditioner
may also
affect medical
equipment, disturbing medical
care, and communications
equip-
ment, harming the screen display
quality.
1.2. Before installation or relocation
Caution:
,, Be extremely
carefum when transporting
the units.Two
or mote persons are
needed to handle the unit as it weighs 20 kg, 44 Ibe or more. Do not grasp the
packaging
bands. Wear protective
gloves
as you can injure your hands
on
the fins or other parts.
,, Be sure to safely dispose
of the packaging
materials.
Packaging
materiame,
such as naims and other
metam or wooden
parts may cause
stabs or other
injuries.
o Thermal insulation of the refrigerant pipe is necessary to prevent condensa-
tion. if the refrigerant pipe is not properly insulated, condensation
will be formed.
o Place thermal
insulation
on the pipes to prevent condensation,
if the drain-
pipe is installed
incorrectly, water leakage and damage to the ceiling,
floor,
furniture,
or other possessions
may result.
, Do not clean the air conditioner
unit with water. Electric
shock may result.
, Tighten all flare nuts to specification
using a torque
wrench.
If tightened
too
much, the flare nut can break after an extended
period.
1.3. Before electric work
Caution:
,, Be sure to install circuit
breakers,
if not installed, electric shock may result.
,, For the power lines, use standard
cables of sufficient
capacity.
Otherwise,
a
short circuit,
overheating,
or fire may result.
,, When installing
the power
lines, do not apply tension
to the cables.
o Be sure to ground
the unit. if the unit is not properly
grounded,
electric shock
may result.
, Use circuit
breakers
(ground
fault interrupter,
isolating switch (+B fuse), and
molded
case circuit
breaker)
with the specified capacity.
If the circuit
breaker
capacity
is larger than the specified
capacity,
breakdown
or fire may result.
1.4. Before starting the test run
/_
Caution:
,, Turn on the main power switch more than 12 hours before starting operation.
Starting
operation
just after turning
on the power switch
can severely dam-
age the internal parts.
, Before
starting operation, check
that all panels, guards
and other protective
parts are correctly
installed. Rotating,
hot, or high voltage parts can cause
injuries.
o Do not operate the air conditioner
without the air filter set in place, if the air
filter is not installed, dust may accumulate
and breakdown
may result.
, Do not touch
any switch with wet hands. Electric
shock
may result.
, Do not touch
the refrigerant
pipes with bare hands during
operation.
, After stopping operation, be sure to wait at least five minutes before turning
off
the main power switch. Otherwise,
water meakage or breakdown
may resumt.
2