CALCULATION OF WORKING OUTPUT OF THE BURNER
To calculate the burner's working output, in kW, proceed as follows:
- Check at the meter the quantity of supplied litres and the duration,
in seconds, of the reading, then calculate the burner's output through
the following formula:
WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out
together with a combustion analysis, to be executed through suitable devices, taking care that the values are the correct
ones and are in accordance with the local safety regulations. The adjustments must be carried out by qualified and skil-
led technicians authorised by Ecoflam S.p.A.
The adjustment of the position of the firing head is made to obtain the best combustion performance. When used at
the minimum power output the firing head is move back, whilst is forwarded at the maximum output. Execution : -
loosen the locking screw of adjusting device A; - move the adjusting device until the desired position is reached; - tigh-
ten the locking screw.
A
POSITION OF ELECTRODES
BLU 500-700-1000
Ignition electrode
BLU 1200-1400

COMBUSTION ADJUSTMENT

SETTING THE FIRING HEAD
in.
ax.
BLU 500 ÷ 1000
Ignition electrode
Ionization probe
REMOVING THE NOSEPIECE
Ionization probe
pag.19
LB 381 BLU 500 -1400 PR / MD
e =
s =
e x f = kW
f
s
A
in.
BLU 1200 - 1400
B
Litres of gas
Time in seconds
G20 = 34,02
G25 = 29,25
G30 = 116
G31 = 88