ELECTRICAL AND CONTROL SETTINGS
5 ELECTRICAL AND CONTROL SETTINGS
5.1 GENERAL CHECK
•
Make sure that the following conditions related to power supply installation are satisfied:
-
The power capacity of the electrical installation is large enough to support the power demand of the YUTAKI system (outdoor
unit + indoor unit + DHW tank (if apply)).
-
The power supply voltage is within ±10% of the rated voltage.
-
The impedance of the power supply line is low enough to avoid any voltage drop of more than 15% of the rated voltage.
•
Following the Council Directive 2004/108/EC, relating to electromagnetic compatibility, the table below indicates the Maximum
permitted system impedance Z
Indoor unit alone
Power
Model
supply
Without DHW tank heater
RWH-4.0VNFE
1~
Without DHW tank heater
RWH-5.0VNFE
230V
50Hz
Without DHW tank heater
RWH-6.0VNFE
Without DHW tank heater
RWH-4.0NFE
3N~
Without DHW tank heater
RWH-5.0NFE
400V
50Hz
Without DHW tank heater
RWH-6.0NFE
?
N O T E
The data corresponding to DHW tank heater is calculated in combination
with the YUTAKI S80 domestic hot water tank accessory "DHWT-
(200/300)S-3.0H2E".
The status of Harmonics for each model, regarding compliance with IEC 61000-3-2 and IEC 61000-3-12, is as follows:
Status regarding compliance with
IEC 61000-3-2 and IEC 61000-3-12
Equipment complying with IEC 61000-3-2
Equipment complying with IEC 61000-3-12
Installation restrictions may be applied by
supply authorities in relation to harmonics
14
PMML0340B rev.1 - 03/2016
at the interface point of the user's supply, in accordance with EN61000-3-11.
max
Operation mode
Z
max
0.31
With DHW tank heater
0.20
0.27
With DHW tank heater
0.18
0.24
With DHW tank heater
0.17
With DHW tank heater
0.38
With DHW tank heater
0.38
With DHW tank heater
0.38
Models
RWH-4.0NFE
RWH-5.0NFE
RWH-6.0NFE
RWH-4.0NFWE
RWH-5.0NFWE
RWH-6.0NFWE
RWH-4.0VNFE
RWH-5.0VNFE
RWH-6.0VNFE
RWH-4.0VNFWE
RWH-5.0VNFWE
RWH-6.0VNFWE
-
Indoor unit in combination with DHW tank
(Ω)
Model
RWH-4.0VNFWE
RWH-5.0VNFWE
RWH-6.0VNFWE
-
RWH-4.0NFWE
-
RWH-5.0NFWE
-
RWH-6.0NFWE
?
N O T E
The data corresponding to DHW tank heater is calculated in combination
with the YUTAKI S80 domestic hot water tank accessory "DHWS(200/260)
S-2.7H2E".
•
Check to ensure that existing installation (mains power
switches, circuit breakers, wires, connectors and wire
terminals) already complies with the national and local
regulations.
•
The use of the DHW tank heater is disabled as factory
setting. If it is desired to enable the DHW tank heater
operation during normal indoor unit operation, adjust the
DSW4 pin 3 of the PCB1 to the ON position and use the
adequate protections. Refer to the section
switches and RSW switches"
Power
Operation mode
supply
Without DHW tank heater
With DHW tank heater
1~
Without DHW tank heater
230V
With DHW tank heater
50Hz
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
With DHW tank heater
3N~
Without DHW tank heater
400V
With DHW tank heater
50Hz
Without DHW tank heater
With DHW tank heater
"5.6 Setting of DIP
for the detailed information.
Z
(Ω)
max
0.31
0.21
0.27
0.19
0.24
0.17
-
0.41
-
0.41
-
0.41