Lamborghini Caloreclima 55 PM/M-E Manual De Instalación Y Mantenimiento página 64

Quemadores a gas modulantes con dos etapas progressivas
Ocultar thumbs Ver también para 55 PM/M-E:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

DIAGRAM OPERATION TWO PROGRESSIVE STAGES
TC
PG
MB
PA
TR
VE
max.
M
MT
min.
EC
Legend
T11 Air shutter opening time, from 0 to max.
TW Begins with the closure of the thermostatic line
or the PG. The PA must be in the rest position.
This is the waiting and self-test time.
T10 Begins when the motor starts up and with the
pre-purge phase, within which the PA air
pressure switch must give the go-ahead.
Pre-purge time.
T1
T3
Pre-ignition phase, it ends when the gas valve
opens.
Input signals
Output signals
A
Begin start up
Flame present
B
Operation
B-C
C
Control stop
Air shutter closure + post-purge
C-D
Thermostats/Gas pressure switch line
TC-PG
T10
TW
T11
T1
0
T3
T2
T12
T4
T2
Safety time, within which the flame signal must
reach the EC electrode.
T4
Interval between the opening of the gas valve
and the opening of the second stage.
Air shutter closing time and program zero-setting
T6
time.
T12 Time in which the air shutter shifts to the start-up
position.
MB
PA
TR
VE
EC
MT
Burner motor
Air pressure switch
Ignition transformer
Gas valve
Control electrode
Air servo control
64
T6
Tabla de contenido
loading

Este manual también es adecuado para:

70 pm/m-e90 pm/m-e140 pm7m-e140 pm/m-e210 pm/m-e

Tabla de contenido