7 Troubleshooting

Depending on PSE Softstarter configuration, different events may be
signalled on the LCD. All event codes are found in table 7.1: Event list.
Table 7.1: Event list
Event
Event
code
SF20
Software fault
Shunt fault
SF3x
1
By-pass open
SF4x
1
SF50
Softstarter thermal overload
Phase loss fault
EF1x
1
EF20
Bad network quality
Current lost fault
EF3x
1
EF40
Fieldbus fault
EF50
Low supply voltage
High current fault
EF6x
1
P1
Motor overload protection
P2
Underload protection
P3
Locked rotor protection
SF = Softstarter fault
EF = External fault
P = Protection
x = phase number, 4 indicates multiple or unknown phase
1
Cause
Fault in software
By-pass relay does not open or thyristor short
circuit
By-pass relay or by-pass contactor does not
close
Thyristors overheated
Power loss on operational current on one or
several phases
Excessive disturbances in the operational sup-
ply network
Operational current on one or several phases
lost
Fault on Fieldbus communication
Voltage too low or briefly interrupted in supply-
ing network for softstarter
Operational current higher than 8 x I e
Load on motor higher than motor rating and
corresponding selected EOL Class.
Current limit parameter is set on a too low
value.
Load on motor too low
Load on motor too high for a short time
Softstarters Type PSE18...PSE370 User Manual short form 1SFC132059M9901 15