AKD Product Safety Guide | 1 English
1.5.7.5 STO technical data AKD-x048
Safety characteristic data
Device Operation mode
STO
STO
STO dual channel with
Pinout
Pin Description
1
2
3
4
For STO single channel mode connect pin 6 with pin 8 and pin 5 with pin 7.
Signal diagram (sequence)
The diagram below shows how to use STO function for a safe drive stop and fault free oper-
ation of the drive.
1. Brake the drive in a controlled manner (speed setpoint = 0 V).
2. When speed = 0 rpm, disable the drive (Enable = 0 V).
3. Activate the STO function (STO-Enable 1 and STO-Enable 2 = 0 V)
20
Kollmorgen | kdn.kollmorgen.com | October 2018
13849-1
single channel
PL d, Cat 2
dual channel
PL d, Cat 3
PL e, Cat 4
periodical testing
+24 VDC Auxiliary voltage
24V Supply GND
STO +24 VDC supply voltage
STO GND
ISO
IEC
62061
SIL 2
1.88E-07
SIL 2
5.64E-09
SIL 3
5.64E-09
Pin Description
5
STO-Status 1
6
STO-Enable 1
7
STO-Status 2
8
STO-Enable 2
PFH
T
SFF
M
[1/h]
[Years]
20
20
20
[%]
89
87
87