INSTALLATION
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
1. Install the power pack according to its instructions.
2. Connect the power pack wires to the sensor as follows:
• RED wire (+24VDC) to the +24V IN terminal on the sensor.
• BLACK wire (Return) to common (COMM.) terminal on the
sensor.
• BLUE wire to control output (CTRL. OUT) terminal on the
sensor.
3. Wire the Isolated Relay.
The Isolated Relay is rated for 1A @ 30VAC/VDC. Connect the
wires necessary to the application that requires this output:
• Normally Closed (N.C.) - Open when occupancy is detected.
Relay Common (must be used for proper operation)
• Normally Open (N.O.) - Closed when occupancy is detected.
NOTE: The bottom terminal on the sensor is not used.
4. Turn the power on.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not
included).
1 2 3
Time Delay
Test/20 min
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Service
4
Walk-Through
Enabled
Disabled
Service bypasses occupancy
& light level functions. Control the
load manually using ON/OFF button.
Sensor Adjustment
Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away
from the unit.
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the
top of the button while pressing it into the unit. Reinstall the cover plate.
Light Level Adjustment
The light level can be set with loads ON or OFF. To enable light level control and set the threshold:
1. Make sure the room is lit appropriately.
2. Put the sensor into TEST mode using the Time Delay DIP Switches.
3. Press and hold the ON/OFF button for 3 seconds, until you hear a beep.
4. Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained,
even if power is lost, until it is re-set or disabled.
5. Set the Time Delay DIP Switches to the desired delay time.
6. To disable light level control, press and hold the ON/OFF button for 7 seconds, until a double beep tone sounds.

DIP SWITCH SETTINGS

ON Mode
Time
Visible
Not Used
Delay
Alerts
ON
Audible Alert
1
2
3
4
5
6
7
8
9
Walk-Through
Audible Alerts
PIR Sensitivity
5
PIR Sensitivity
Low, 50%
High
6
Switch 9 is not used
Visible Alert
Enabled
Disabled
=ON
=Factory Setting
White
Neutral
Black
Hot
ON/OFF Button
7
Enabled
Disabled
8
ON Mode
Manual On
Auto On
Button
Hinges
=OFF
ADJUSTMENTS
3
White (Neutral)
Red (Line)
Power
Pack
+24 VDC
Common
Control Outputs
Normally closed contact
Common
Normally open contact
Not used
PW-100-24 Wiring
Tabs
Lighting
Load
Red
(Load)
Isolated Relay Outputs
DIP Switches
Detection LED
PIR Lens