Accessories; Factory Fitted Accessories; Accessories Supplied Separately - Hitecsa EQU-PF 233 Manual De Instalación, Uso Y Mantenimiento

Ocultar thumbs Ver también para EQU-PF 233:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

o The following is memorised for each alarm:
 date and time of intervention (if the KSC accessory is present);
 in/out water temperature values as soon as the alarm is triggered;
 the condensation pressure values at the time of the alarm
 alarm delay from when the connected device is switched on;
 compressor status at the time of the alarm;
o Advanced functions:
 Hi-Pressure Prevent function with forced cooling capacity
partialisation for a high outdoor temperature (in summer mode),
 set-up for serial connection (KRS485, KFTT10, KRS232, KUSB
accessory);
 possibility to have a digital input for remote management of the
double Set point (see the Pre-sales Department);
 possibility to have an analogue input for the shifting Set-point via a
4-20mA remote signal (contact Pre-sales Department);
 set-up for management of time bands and operating parameters with
the possibility of daily/weekly operating programs (KSC accessory);
 check-up and verification of the scheduled maintenance status;
 computer-assisted machine testing;
 self-diagnosis with continuous monitoring of the machine operating
status.
II.2

ACCESSORIES

II.2.1

Factory fitted accessories

P1 – Installation with pump.
P2 – Installation with increased head pump.
DP1 – Installation with double pump, one of which in standby with
automatic activation.
DP2 – Installation with increased head double pump, one of which in
standby with automatic activation.
ASP1 – Installation with pump and storage tank.
ASP2 – Installation with increased head pump and storage tank.
ASDP1 – Installation with double pump, one of which in standby with
automatic activation and storage tank.
ASDP2 – Installation with increased head double pump, one of which in
standby with automatic activation and storage tank.
INS– Soundproofed compressors with noise-absorbing ear muff
(solution that reduced the noise of the compressors).
RA – Evaporator anti-freeze resistance, prevents the risk of ice
formation inside the exchanger when the machine is switched off
(provided the unit remains powered).
RDR – Desuperheater/recovery unit anti-freeze resistance (DS or
RC100), prevents the risk of ice formation inside the recovery unit
exchanger when the machine is switched off (provided the unit remains
powered).
RAS – 300W storage tank anti-freeze resistance (available for ASP1-
ASDP1- ASP2-ASDP2 set-ups); prevents the risk of ice formation inside
the exchanger tank when the machine is switched off (provided the unit
remains powered).
RAE 1 – 27W electric pump anti-freeze resistance (available for P1-
DP1-ASP1-ASDP1 set-ups); prevents the risk of the water inside the
pump becoming ice when the machine is switched off (provided the unit
remains powered).
RAE 2 – 27W double electric pump anti-freeze resistance (available for
P2-DP2-ASP2-ASDP2 set-ups); prevents the risk of the water inside the
pumps becoming ice when the machine is switched off (provided the
unit remains powered).
SECTION II: INSTALLATION AND MAINTENANCE
DS – Desuperheater; it is not active during heat pump operation.
RC100 – Heat recovery unit with 100% recovery; the accessory is
complete with a differential pressure switch on the recovery unit
exchanger. It does not work as a heat pump.
GM – Cooling circuit high and low pressure gauges.
SFS – Soft-Start device to reduce the peak current in the start-up phase
(weight 40 Kg).
FTT10 – FTT10 serial interface board for connection to supervision
®
systems (LonWorks
system compliant with Lonmark
with chiller profile).
SS – RS485 serial interface board to create dialogue networks between
boards (maximum: 200 units for a max. distance of 1000 m) and the
building automation or external supervision systems.
CR – Power factor correction capacitors (cosΦ > 0.91).
EEV – Electronic thermostatic valve.
RAP – Unit with copper/pre-painted aluminium coils.
BRR – Unit with copper/copper coils.
DSP – Double Set-point via digital consensus (incompatible with the CS
accessory).
BT – low temperature of water produced (only for models 270÷2160).
CS – 4-20 mA analogue signal for shifting Set-point (incompatible with
the DSP accessory). The EEV accessory may have to be also installed,
depending on the required values.
RPB – Coil protection mesh with accident-prevention function.
IMB – Protective packaging.
II.2.2

Accessories supplied separately

KFA - Water filter (only for models 233÷265).
KRAS - Fitting for connection to the inlet duct.
KRMA - Antivibration fitting for connection to the outlet duct.
KSA – Rubber antivibration mountings.
KRIT – Additional electrical resistance heater for heat pump only for
233÷265.
KEAP – Outdoor air temperature probe for Set-point compensation
(incompatible with the CS accessory).
KTR – Remote control keyboard with backlit LCD display (same
functions as that on the machine).
KSC – Clock card to display the date/time and machine time band
management with daily and weekly start/stop time bands, with the
possibility of changing the Set-points.
KRS485 – RS485 serial interface board to create dialogue networks
between boards (maximum: 200 units for a max. distance of 1000 m)
and the building automation or external supervision systems.
KFTT10 – FTT10 serial interface board for connection to supervision
®
systems (LonWorks
system compliant with Lonmark
with chiller profile).
KISI – CAN bus serial interface (Controller Area Network).
KRS232 – RS485/RS232 serial converter for interconnection between
the RS485 serial network and supervision systems with serial
connection to the PC via the RS232 serial port (RS232 cable supplied).
KUSB – RS485/USB serial converter for interconnection between the
RS485 serial network and supervision systems with serial connection to
the PC via the USB port (USB cable supplied).
KMDM – GSM 900-1800 modem kit to be connected to the unit for
remote management of the parameters and any alarm signals. The kit
consists of a GSM modem with relative RS232 board. A SIM data card,
not supplied must be purchased.
KRS – Supervision software for the monitoring and remote
management of the units. The kit consists of a CD-Rom and hardware
key.
10
®
8090-10 protocol
®
8090-10 protocol

Capítulos

Tabla de contenido
loading

Tabla de contenido