Fuel Consumption
See Figure 7 for fuel supply requirements at half and full
load for both natural gas and LP vapor.
Figure 7 — Fuel Supply Requirements
Models
040213-0 & 040234-0
* = Natural Gas is in cubic feet per hour
** = LP Vapor is in cubic feet per hour
Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour
NPT
10ft
15ft
3/4"
346
293
1"
653
549
Natural Gas (sg=0.65)
Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour
NPT
10ft
15ft
3/4"
277
192
1"
428
360
Liquid Propane (LP) (sg=1.50)
INSTALLATION
Natural Gas*
1/2 Load
120
20ft
30ft
40ft
240
192
163
446
360
307
20ft
30ft
40ft
158
126
107
293
236
202
Fuel Pipe Sizing
Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.
Listed values compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, please refer
to federal and local codes.
Full Load
1/2 Load
233
51.30
50ft
60ft
70ft
145
132
120
274
250
230
50ft
60ft
70ft
95
87
79
180
164
151
9
LP Vapor**
Full Load
97.52
+/- 5%
+/- 5%
80ft
90ft
113
106
211
197
80ft
90ft
74
69
139
129
100ft
99
187
100ft
65
123