PLUMBING CONNECTIONS
Connections
The choice and size of the hydraulic lines is left to the designer, who must operate according to the rules of good
workmanship and the current regulations .
To carry out the connections:
- position the hydraulic lines
- tighten the connections using the "wrench against wrench" method (Fig .1 ref . B)
- check for any leakage of liquid
- cover the connections with insulating material (Fig .1 ref . C) .
The hydraulic lines and joins must be thermally insulated . Avoid partial insulation of pipes .
Overtightening can damage the insulation .
For the water seal of threaded connections use hemp and green paste; the use of Teflon tape is recommended in the
presence of antifreeze in the hydraulic circuit .
Fig .1
A
B
C
Fig .2
The units and any plumbing accessories are provided with
a Eurokonos 3/4" connection. If connections with flat seals
are to be used, 2 conversion unions are supplied with the
unit (fig.2).
17