Description Of The Unit - AERMEC FCLI 32 Manual Instalación Y Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

DESCRIPTION OF THE UNIT

MACHINE PURPOSE
The fan coil is a room air treatment terminal unit for both winter and summer operation.
FCLI VERSION
Cassette-type fan coil with Inverter for installation in suspended ceilings; can be integrated in standard 600x600 and
840x840 panelling.
AVAILABLE SIZES
The cassette-type fan coils of the FCLI range are available in:
for 2-pipe systems
FCLI 32 (600x600)
FCLI 42 (600x600)
FCLI 62 (600x600)
FCLI 82 (840x840)
FCLI 122 (840x840)
GRILLE UNIT (OBLIGATORY ACCESSORY)
GLLI100/GLFI10/GLLI100N/GLFI10N/GLFI10M/GLLI100EH/GLFI10EH - GLLI 20 (840x840): Grille unit with suction and delivery filter, with
manually adjustable fins; requires an external control panel with thermostat and ventilation speed control, with 0-10V output.
TECHNICAL DATA AND OPERATING LIMITS
Maximum recommended temperature
Maximum water inlet temperature
Maximum operating pressure
Minimum operating pressure
Room temperature limit R.T.
Room temperature limit R.H.
Minimum delivery (heating)
Maximum delivery (heating)
Minimum delivery (cooling)
Maximum delivery (cooling)
Maximum input current
Power supply
Performance values refer to the following conditions:
- at the maximum motor speed;
Water temperature
In order to prevent air stratification in the
room, and therefore to achieve improved
mixing, it is advisable not to supply the fan coil
Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment where
the relative humidity is high, condensate
might form on the air delivery and
on the outside of the device. This
condensate might be deposited on any
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Ambient air temperature
with wet bulb
For 4-pipe systems
FCLI 34 (600x600)
FCLI 44 (600x600)
FCLI 64 (600x600)
FCLI 124 (840x840)
FCLI
32
°C
100
°C
750
400
°C
100
100
°C
750
750
0.22
0.22
A
V / Hz
- the total input power is determined by adding the input power
for the unit to the input power for the accessories connected and
declared in the corresponding manuals.
with water at a temperature over 65°C.
The use of water at high temperatures
could cause squeaking due to the different
thermal expansions of the elements (plastics
objects underneath and on the floor.
To avoid condensate on the external struc-
ture of the apparatus with the fan in
operation, the average temperature of
the water must not be lower than the lim-
its shown in the table below, that depend
on the thermo-hygrometric condition of
15
17
19
21
23
34
42
44
62
65°C
80°C
kPa 800 (8 bar)
kPa 100 (1 bar)
<Ta<40
0°C
°C
< 85%
R.H.
50
100
50
150
750
400
1050
100
100
150
750
750
1050
0.33
0.33
0.37
230V (±10%) 50 Hz
and metals), this does not however cause
damage to the unit if the maximum operating
temperature is not exceeded.
the air in the environment.
The limits mentioned above refer to opera-
tion while the fan is set
to its minimum speed level.
Ambient air temperature with dry bulb
21
23
25
3
3
3
3
3
3
3
3
3
6
5
4
-
8
7
64
82
122
124
50
250
350
50
400
1750
2450
400
150
250
350
250
1050
1750
2450
1750
0.37
0.7
0.75
0.75
230V (±10%) 50/60 Hz
27
29
31
3
3
3
3
3
3
3
3
3
3
3
3
6
5
5
21

Capítulos

Tabla de contenido
loading

Tabla de contenido