ENGLISH
Installation
Fig. 2,3
Note:
the positioning of the two sensors is important in order to correctly measure the temperatures: one sensor must be
installed if possible at the highest point of the environment and preferably not near any openings in the ceiling, while
the other sensor must be installed on the floor, preferably not near doors or windows. Sensors should not be
covered by curtains or other objects. The system can also be installed inside large spaces (industrial sheds), as
each fan constitutes a node that acts as a repeater for the neighbouring node, should it be too far from the control
unit to be directly controlled by it. Sensor connection can be carried out using a common cable available on the
market with two wires (0.5 mm2). Use a cable with a diameter of at least 1.5 mm2 for lengths exceeding 15 metres.
The maximum allowed length is 50
2 2
*
SCREWS, WASHERS AND PLUGS FOR WALL MOUNTING ARE NOT INCLUDED.
3 3
m.
Probe
Probe
Heating
System Power
supply
*
17