Return To Service - Generac 70430 Manual Del Propietário

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

4.10.2— Return to Service
To return the unit to service after storage:
1.
Verify that utility power is turned off.
2.
Check the tag on the engine for oil viscosity and classification. If necessary, drain and refill with proper oil.
3.
Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT use tap water. Recharge the
battery to 100% state of charge. If defective, replace the battery.
4.
Clean and wipe down the entire generator.
5.
Make sure the 7.5 Amp
ATO
6.
Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly. Install positive cable first.
7.
Reconnect the battery charger AC input T1/Neutral cable (has white sleeve) at controller.
8.
Open the fuel shutoff valve.
®
9.
Insert the 7.5 Amp
ATO
10. Start the unit by pressing the MANUAL button. Allow the unit to warm up for a few minutes.
11. Stop the unit by pressing the Control Panel OFF button.
12. Turn on the utility power to the transfer switch.
13. Set the Control Panel to AUTO.
The generator is ready for service.
NOTE: When a battery is dead or has been disconnected, the exercise timer and current date and time must be reset.
28
®
fuse is removed from the generator Control Panel.
fuse into the generator Control Panel.
Automatic Standby Generator Owner's Manual
Tabla de contenido
loading

Tabla de contenido