Service Menu - Lamborghini Caloreclima NINFA 24 MCS Instrucciones De Uso, Instalación Y Mantenimiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 92

Service Menu

The card Service Menu is accessed by turning the selector (detail 3 - fig. 1) to RESET for 10 seconds and then to
(winter) or
(summer). Use the heating knob (detail 1 - fig. 1) to select "tS", "In", "Hi" or "rE". "tS" means Transparent
Parameters Menu, "In" means Information Menu, "Hi" means History Menu, "rE" means History Menu Reset. After se-
lecting the Menu, to access it turn the selector (detail 3 - fig. 1) to RESET for 1 second and then to
(summer).
"tS" - Transparent Parameters Menu
The card has 24 transparent parameters modifiable also from Remote Timer Control (Service Menu):
Table. 2
Remote
Card
Description of Transparent Parameters
Control
01
P01
Type of gas selection
02
P02
Not used
03
P03
Absolute min. power
04
P04
Lighting power
05
P05
Not used
06
P06
Heating system train
07
P07
Post Circulation heating system
pump
08
P08
Heating wait time
09
P09
Max. heating power
10
P10
Pump operation
11
P11
Pump switching off temperature during Post Cir-
culation
12
P12
Max. user setpoint in heating
13
P13
Post Circulation DHW circuit pump
14
P14
DHW circuit wait time
15
P15
Max. power in hot water production
16
P16
Max. user setpoint in hot water production
17
P17
Comfort activation temperature
18
P18
Comfort deactivation hysteresis
19
P19
Burner turning off in hot water production
20
P20
Not used
21
P21
Not used
22
P22
Not used
23
P23
Not used
24
P24
Mains Voltage Frequency
With the heating knob (detail 1 - fig. 1) it is possible to scroll the list of parameters, in increasing or decreasing order
respectively. To modify the value of a parameter just turn the DHW knob (detail 2 - fig. 1): the modification will be auto-
matically saved.
To go back to the Service Menu turn the selector (detail 3 - fig. 1) to RESET for 1 second and then to
(summer). To exit the card Service Menu turn the selector (detail 3 - fig. 1) to RESET for 10 seconds and then to
(winter) or
(summer).
50
Range
0=Natural Gas, 1=LPG
Not modifiable
0-100%
0-60%
Not modifiable
1-20°C/min
0-20 minutes
0-10 minutes
0-100%
0=Post Circulation
1=Continuous
0-100°C
31-85°C
0-255 seconds
0-255 seconds
0-100%
55-65°C
0-80°C
0-30°C
0=Fixed, 1=Linked to setp., 2= For
solar system1, 3= For solar system2
Not modifiable
Not modifiable
Not modifiable
Not modifiable
0=50Hz, 1=60Hz
cod. 3540F611 - 05/2007 (Rev. 00)
NINFA 24 MCS
(winter) or
Default
0=Natural Gas
1
0%
50%
0
5°C/min
6 min
2 minutes
100%
0=Post Circulation
33°C
85°C
30 seconds
120 seconds
100%
55°C
40°C
20°C
1=Linked to setp.
4
8
0
0
0=50Hz