Sears Kenmore 78079 Manual Del Propietário página 19

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation
Figure 34. Securing Outer Case in Wall Opening
1. Lintel and flashing (if required)
2. Provide
3
/
" slope to outside for condensate drainage
8
3. Attach outer case to framing in two places on each
side of case
4. Completely caulk or seal all four sides of outer case
5. Outer case extends into room ¾"
5
Masonry Construction
See Figure 32 for dimensions of finished opening to cut
out or build into masonry wall. Seal outer case in place
with mortar or secure to wall with concrete nails driven
through sides of case.
NOTE: If securing case with concrete nails, pre-drill
holes in case before driving nails into wall.
Installation in Walls Exceeding
Outer Case Dimensions
Air conditioner must be installed so air flows freely
through side louvers to prevent overheating of
compressor and fan motor. If dimensions of wall restrict
airflow to louvers, wall opening must be modified by
chamfering vertical portions of outside opening, as
shown in Figures 35 and 36.
1
2
3
4
Figure 35. Chamfering Walls That Exceed Outer Case
Dimensions (Top View)
1. Outer case extends into room ¾"
2. Distance from front of outer case to side louvers
12000 Btu
9 inches
3. Caulk around outer case to seal in place
4. Mortar
5. 4" clearance required for unrestricted air flow
6. Side louvers
1
2
5
Figure 36. Chamfering Walls That Exceed Outer Case
Dimensions (Side View)
1. Outer case extends into room ¾"
2. Distance from front of outer case to side louvers
12000 Btu
9 inches
3. Caulk around outer case to seal in place
4. Install outer case with
5. Install lintel and/or flashing, if necessary
5
4
3
19
18000 Btu
14½ inches
3
4
6
5
18000 Btu
14½ inches
3
/
" slope to outdoor side
8
2
1
Tabla de contenido
loading

Este manual también es adecuado para:

Kenmore 78098Kenmore 70089Kenmore 70129Kenmore 78189

Tabla de contenido