Installation Dimension; Installation The Unit - Fujitsu Airstage ARXC36GATH Manual De Instalación

Ocultar thumbs Ver también para Airstage ARXC36GATH:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 44
(1) Install the indoor unit on a place having a suffi cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(5) Install the unit where the connection pipe can be easily installed.
(6) Install the unit where the drain pipe can be easily installed.
(7) Install the unit where noise and vibrations are not amplifi ed.
(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
(9) Do not install the unit where it will be exposed to direct sunlight.
] 1

3.2. Installation dimension

Install at least 20 mm from the ceiling.
Provide a service hole for inspection purposes as shown below.
Do not place any wiring or illumination in the service space, as they will impede service.
Unit
30 mm or more
: Service hole
1

3.3. Installation the unit

Install the air conditioner in a location which can withstand a load of at least 5 times
the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
Confi rm the directions of the air intake and outlet before installing the unit.
The unit takes in air from the evaporator side, and expels it from the fan side.
3.3.1. Installing the hangers
Hanging bolt installation diagram.
400 mm
155 mm
En-3
9373870111-01_IM.indb Sec1:3
9373870111-01_IM.indb Sec1:3
AIR
AIR
500 mm
or more
: Service space
WARNING
CAUTION
1,050 mm
85 mm
1,000 mm
AIR
AIR
AIR
1,080 mm
Hanging bolt M10
(Field supply)
Washer
(Field sup-
ply)
CAUTION
Fasten the unit securely with special nuts A and B.
3.3.2. Leveling
Use the procedure in the following fi gure to adjust the levelness.
Level meter
B
(Front)
B
(Side)
The side A of the unit with the drain port should be slightly lower than the opposite side B
of the unit. The height difference between sides A and B should be from 0 to 20 mm.
3.3.3. Mounting the duct
Follow the procedure in the following fi gure to install the ducts.
324 mm
14 mm
14 mm
27 mm
26 mm
295 mm
Spacing between fl ange and drain pan.
Special nut A (Large)
(Accessories)
Hanger
Special nut B (Small)
(Accessories)
A
Level meter
A
862 mm
Intake port fl ange
Outlet port fl ange
851 mm
2012-7-12 14:19:00
2012-7-12 14:19:00
Tabla de contenido
loading

Este manual también es adecuado para:

Airstage arxc45gathAirstage arxc60gath

Tabla de contenido