DIP-SWITCH SETTINGS (D, fig. 5, pag. )
DIP 1:
On => automatic re-closing enabled.
Off => automatic re-closing disabled.
DIP 2:
On => "manual mode" activated.
Off => "manual mode" deactivated.
DIP 3:
On => TD mode: "open-close" with inversion only during the opening stage.
Off => TD mode: "open-block-close-block".
NOTE: to set the dip-switches; turn off the power to the programmer, change the setting and then switch the
power back on.
WORK TIME PROGRAMMING (LIMITED OPENING, OPENING AND PAUSE)
1) With the gate completely closed, press and hold down the "PR" button for 4 seconds. The led "LPR" will be
off to start with and will then start to flash rapidly indicating that the programming mode has been entered. The
indicator light will flash intermittently at the same frequency as the indicator led. Release the "PR" button.
NOTE: if you press the "PR" button and the led "LPR" lights up straight away it means that the programmer is not
completely closed and you cannot therefore enter the programming mode; Switch the power off and on again.
If the security devices (TB, FTCI, FTCS) are not at rest time programming will not be enabled.
During time programming the activation of (TB, FTCI, FTCS) will cause the gate and the time count to block. They
will continue as soon as the security devices are once again at rest. Each time the gate and time count start again
the electric lock will cut in.
2) Press the "PR" button (or activate either "TD" or the radio control) and keep it pressed until the gate has reached
the desired limited opening position. When you release the button the gate will block and will start to move again
(and count the work time) after a one second period has elapsed.
3) When the opening travel limit is activated the motor will block but the work time count will carry on in order to
give a slightly higher time margin with respect to the exact manoeuvring time.
4) Press the "PR" button (or activate either "TD" or the radio control): the work time count will end. The indicator
light is now flashing at slower intervals: the pause time count has now started.
5) When the pause time is sufficient, press the "PR" button again (or activate either "TD" or the radio control) the
closing cycle will start and you will exit the programming procedure.
***** READ THE FOLLOWING NOTES CAREFULLY *****
• When the unit is powered up; if the opening travel limit is active and automatic re-closing has been selected the
gate/door will close after the pause period has expired.
• When the unit is powered up with the gate/door not completely closed the logic will only allow the opening
command and not the closing command. The only exception occurs when the opening travel limit is active.
• With the barrier fully open, activating FTCI or TA will force a pause time reset.
• The limited opening command can only be used when the gate is completely closed. You cannot therefore give
two successive limited opening commands. If the FTCI activates during the closing stage the reopening will still
be limited (the gate will not reopen completely).
INDICATOR LIGHT FUNCTION MODE
The indicator light output (24V ac, 3W) is used to indicate the gate status.
• When the gate is completely closed
• When the gate is opening
• When the gate is closing
• When the gate has stopped (but is not completely closed)
ALARM INDICATIONS
) Wrong parameters in EEPROM memory
If there is a data read error from EEPROM the indicator light will indicate the error by activating intermittently: the
system will be blocked. You will have to enter work time programming to correct the error. Pressing the "PR" button
will force the LED "LPR" to flash straight away.
2) Simultaneous travel limit activation
Simultaneous travel limit activation will cause the programmer to block as long as the problem exists. The warning
light will stay ON for 3 seconds and OFF for 3 seconds.
When the travel limits have been freed an automatic RESET will occur and normal operation will return.
The indicator light is off
The light flashes slowly
The light flashes quickly
The indicator remains lit