2. IMPORTANT SAFETY WARNINGS
START-UP AND COMMISSIONING
An authorized Tripp Lite engineer must perform the start-up of the UPS and a completed start-up form must be returned to
Tripp Lite in order to activate the SmartOnline SV warranty. Please contact your local supplier or [email protected]
for further details. To find your local contact, go to www.tripplite.com/support/contacts.
This UPS contains LETHAL VOLTAGES. KEEP DOORS LOCKED AT ALL TIMES. All repairs, service and installation must be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
• Ensure all power is disconnected before performing installation or service.
• The UPS system contains its own energy source (battery). The output terminals may carry live voltage even when the UPS is disconnected from
an AC source.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended.
• The Protective Earth Ground must be installed first prior to any power connections made to the equipment.
• Installation and wiring must be performed in accordance with local electrical laws and regulations.
• The AC disconnection device must break line and neutral conductors: four connectors for three phases (L1, L2, L3 and N).
• The DC disconnection device must break line with both the positive and negative conductors.
• A readily accessible, external disconnect device to the equipment shall be provided for the AC and DC supplies in the end installation.

2.4 Battery Warning

This UPS contains LETHAL VOLTAGES. The UPS is designed to supply power even when disconnected from utility power. Only AUTHORIZED
SERVICE PERSONNEL should access the interior of the UPS, after disconnecting the utility and DC power.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed
only by qualified service personnel, observing proper precautions. Turn off the UPS before connecting or disconnecting internal batteries. Use
tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.
• The batteries are recyclable. Refer to local codes for disposal requirements or visit http://www.tripplite.com/support/recycling-program for
recycling information.
• Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings. Escaping electrolytes may be toxic and cause
injury to skin and eyes.
• Do not disconnect the batteries while the UPS is in battery mode.
• Disconnect the charging source prior to connecting or disconnecting terminals.
• The following precautions should be observed:
1. Remove watches, rings and other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries or battery cabinets.
5. Determine whether the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded
battery can result in electric shock. The likelihood of an electric shock is reduced if such grounds are removed during installation and
maintenance.
• Battery replacement should be performed only by authorized service personnel, using the same number and type of batteries
(sealed lead acid).
• If the UPS system remains off for an extended period of time, it should be turned on periodically and the batteries should be fully charged.
See Section 14.1 UPS and Battery Storage for battery storage recommendations. Failure to recharge the batteries may cause irreversible
battery damage.

2.5 Safety Standards

Item
Uninterruptible power systems (UPS)
Notes:
Conducted
Radiated
Normative reference
UL 1778, CSA C22.2 No.107.3-14
FCC Part 15, Subpart B Class A
FCC Part 15, Subpart B Class A