ELECTRICAL DATA – ALL UNITS SSR UP6–40–HA
Standard voltage
PACKAGE
Motor enclosure
Power (nominal)
Full load current at maximum
pressure
Full load current at maximum
pressure with dryer option
Starting current FV (STAR)
Starting current FV (STAR)
with dryer option
Starting time FV (STAR)
Starts per hour (maximum)
ELECTRICAL DATA – FV / Star Delta
Control voltage
Minimum fuse rating
See note 1
Minimum fuse rating with dryer
option
See note 1
Minimum wire size AWG
See note 2
ELECTRICAL DATA – ALL UNITS SSR 30E–HA
Standard voltage
PACKAGE
Motor enclosure
Power (nominal)
Full load current at maximum
pressure
Full load current at maximum
pressure with dryer option
Starting current FV (STAR)
Starting current FV (STAR)
with dryer option
Starting time FV (STAR)
Starts per hour (maximum)
ELECTRICAL DATA – FV / Star Delta
Control voltage
Minimum fuse rating
See note 1
Minimum fuse rating with dryer
option
See note 1
Minimum wire size AWG
See note 2
200V
230V
ODP
TEFC
ODP
136.0A
128.3A
119.0A
123.5A
706 (265)
617 (231)
652 (268)
175A
150A
175A
4/0
3/0
200V
230V
ODP
TEFC
ODP
109.2A
100.9A
95.0A
99.5A
567 (212.4)
493.2 (184.8)
516.6 (193.5)
150A
125A
125A
150A
3/0
1/0
INSTALLATION / HANDLING
380V
TEFC
ODP
TEFC
40HP
111.5A
71.6A
65.1A
116.0A
374 (140)
3–5 Sec (7–10 Sec)
6
120VAC
90A
150A
2
380V
TEFC
ODP
TEFC
30HP
87.8A
57.5A
53.1A
92.3A
298.5 (111.8)
3–5 Sec (7–10 Sec)
6
120VAC
125A
75A
75A
150A
3
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
460V
575V
ODP
TEFC
ODP
59.5A
56.9A
47.6A
61.7A
58.1A
309 (115)
247 (93)
323 (131)
75A
60A
80A
75A
3
4
460V
575V
ODP
TEFC
ODP
47.5A
43.9A
38.0A
49.7A
46.1A
246.6 (92.4)
197.3 (73.9)
258 (96.7)
60A
60A
50A
75A
75A
4
6
HP50–PE, HXP50–PE
19
TEFC
44.7A
TEFC
38.3A
50A