Fig. IV-08 – Diagramas de flujo de arbitraje de puntos de configuración Auto/stop externo
Auto
External Auto/Stop
Auto
BAS
On-Line
Run if Auto Remote
switch is set in
TechView and Tracer
enable and if load
exists (differential to
start)*
Notes:
*Mode transition from disable to enable shall start unit if LWT>CWS regardless of differential to start. Subsequent starts during Tracer enable will
include differential to start criteria.
**if Tracer communication is lost for 15 minutes, the auto/off mode will be determined by a user defined configuration parameter to allow
1) last sent mode
2) off
3) auto
RTAC-SVX001A-ES
Instalación eléctrica
DynaView or
EasyView
Auto Local or
Comm Loss
(use defaults)**
(differential to start)
Stop
Stop
Run only if
load exists
Stop
56