Mitsubishi Electric CITY MULTI PMFY-P-20-VBM-E Para El Instalador página 8

Ocultar thumbs Ver también para CITY MULTI PMFY-P-20-VBM-E:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
. Installing the grille
Fig. 5-2
Fig. 5-3
Fig. 5-4
Fig. 5-5
8
A Points for securing the grille
B Points for securing the grille
C Indoor unit
D Ceiling surface
5.2. Checks before setting in place (Fig. 5-2, 3)
• Before installing the front panel, make sure the indoor unit is square with the ceil-
ing opening (or parallel to the angle between the wall and the ceiling).
• Check that the four points where the front panel will be secured are in contact
with the ceiling surface.
• Check that the insulation for the refrigerant pipes, drainage pipes, etc. is in place
and that wiring connections and arrangements are complete.
5.3. Installing the grille (Fig. 5-4)
• Open the intake grille by pressing on the place marked Push, and remove the air
filter.
• Remove the screw cover in the middle of the blower.
• Open the upper and lower flaps on the indoor unit completely.
• Hook the temporary holding tabs on the front panel to the hooks on the indoor
unit.
A Hooks
B Open the upper and lower flaps completely.
C Temporary holding tab
D Temporary holding tab
E Screw cover
• Adjust the front panel so that it fits properly in the angle between the ceiling and
the wall, and install the securing bolts 2 (supplied with this grille) in their four
places at left and right, leaving them slightly loose. (Fig. 5-5)
• Next tighten the securing bolts 2 and securing screws 3 in the centre three
places.
• Finally tighten the securing bolts 2 in the four places at left and right.
• At this point, make sure there are no gaps between the indoor unit and the front
panel, and between the front panel and the ceiling surface. If there are gaps, the
wind may come in and it may cause water to drip (Fig. 5-6).
* Tighten the securing bolts 2 and securing screws 3 completely.
• Replace the air filter and screw cover, and press the intake grille on the place
marked Push until you hear it snap into place.
[Fig. 5-5]
A Hooks
D Temporary securing tab
E Drainage pan
F Places for securing front grille
G Make sure these surfaces are flush with
each other (0 - 3 mm).
Tabla de contenido
loading

Tabla de contenido