Installation and Connection
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the plug-in module connector with shielded cable and separated from the
other wiring (power, command in 110 V / 220 Vac, etc), according to item
Separation
Distance. If those cables must cross other cables, it must be done in
perpendicularly among them, keeping the minimum separation distance of 5 cm at
the crossing point.
Connect the shield according to the figure below:
4. Relays, contactors, solenoids or coils of electromechanical brake installed close
to the inverters may occasionally generate interference in the control circuitry. To
eliminate this effect, RC suppressors (with AC power supply) or freewheel diodes
(with DC power supply) must be connected in parallel to the coils of these devices.
5. When using the external HMI (refer to section
connects to the inverter must be separated from the other cables in the installation,
keeping a minimum distance of 10 cm.
6. When using analog reference (AI1) and the frequency oscillates (problem of
electromagnetic interference), interconnect the GND of the connector of the plug-in
module to the inverter grounding connection.
3.2.6 Cable Separation Distance
Provide separation between the control and power cables and between the control
cables (relay output cables and other control cables) as per
Inverter Output
Rated Current
20 | CFW501
Inverter
side
Figure 3.5: Connection of the shield
Table 3.3: Cable separation distance
Length
of the Cable(s)
≤ 100 m (330 ft)
≤ 24 A
> 100 m (330 ft)
≤ 30 m (100 ft)
≤ 28 A
> 30 m (100 ft)
Insulate with tape
Do not ground
7.2 -
Accessories), the cable that
table
3.3.
Minimum
Separation
Distance
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
3.2.6 - Cable