5.3 PREVENTIVE MAINTENANCE

DANGER!
Always turn off the mains power supply before touching any
electrical component associated to the braking module.
High voltage may still be present even after disconnecting the
power supply.
To prevent electric shock, wait at least 10 minutes after turning off
the input power for the complete discharge of the power capacitors.
Always connect the equipment frame to the protective ground (PE).
Use the adequate connection terminal at the braking module.
ATTENTION!
The electronic boards have electrostatic discharge sensitive components.
Do not touch the components or connectors directly. If necessary, first
touch the grounded metallic frame or wear a ground strap.
Do not perform any withstand voltage test!
When installed in proper environment and operating conditions, the braking modules
require little maintenance.
Table 5.2: Recommended periodic inspections - Every 6 months
Component
Terminals, connectors
Fans / Cooling system
Printed circuit boards
Power module /
Power connections
Heatsink
For the DBW03, it is recommended to replace the fans after 50.000 hours of operation.
figure 5.1 illustrates this procedure. It is suggested to perform the cleaning every 6
months of operation, after the module start-up.
If necessary, consult WEG.
Abnormality
Loose screws
Loose connectors
Dirty fans
Abnormal acoustic noise
Blocked fan
Abnormal vibration
Dust in the cabinet air filter
Dust in the cabinet air filter
Odor
Accumulation of dust, oil, humidity, etc. Cleaning
Loose connection screws
Dust accumulation
Dirty
Faults
Corrective Action
Tighten
Cleaning
Replace the fan. Refer to
the figure 5.1. Check the
fan connections.
Cleaning or replacement
Cleaning
Replacement
Tighten
Cleaning
DBW03 | 31