not aligned. Proceed accordingly.
2) Check that the electronic equipment is correctly supplied with power.
Check the integrity of the fuses.
3) Check that the functions are correct by means of the control unit
diagnosing leds (see relevant instructions). Identify any causes for
faults. If the leds show a persistent start command, check that no radio
controls, start buttons or other control devices keep the start contact
activated (closed).
4) If the control unit does not work, it must be replaced. Should the checks
listed above be satisfactory, replace the actuator.
22.2) The gate does not open. The actuator vibrates but there is no
movement.
1) The manual release was left engaged. Reset motorised operation.
Should an electric lock be fitted, check that it opens correctly after the
start command.
2) Check that the capacitor is connected to the motor drive terminals.
3) Check that the motor common (light blue wire) is properly connected.
4) Disconnect and reconnect the power supply to the system. The first start
command must open. Should the actuator close, reverse the respective
drive connections to the actuator.
5) Help the leaf to open by hand. If the leaf opens, check if there are any
mechanical problems with the leaf or, if necessary, adjust the by-pass
valves as described in the relevant item 12. Should the checks listed
above be satisfactory, replace the actuator.
WARNINGS
Correct controller operation is only ensured when the data contained
in the present manual are observed. The company is not to be held
responsible for any damage resulting from failure to observe the
installation standards and the instructions contained in the
present manual.
The descriptions and illustrations contained in the present manual
are not binding. The Company reserves the right to make any alterations
deemed appropriate for the technical, manufacturing and commercial
improvement of the product, while leaving the essential product
features unchanged, at any time and without undertaking to update
the present publication.
TABLE 1
Mod.
Block type
SUB EL
electric lock
SUB
hydraulic blocks
SUB R
hydraulic blocks
SUB E
electric lock
SUB ER
electric lock
SUB G
hydraulic blocks
SUB GR
hydraulic blocks
SUB GE
electric lock
SUB GER
electric lock
INSTALLATION MANUAL
Pump flow rate l/min
Opening angle (degrees)
0.4 (V0)
130°
0.6 (V1)
130°
0.9 (V2)
130°
0.6 (V1)
130°
0.9 (V2)
130°
0.6 (V1)
180°
0.9 (V2)
180°
0.6 (V1)
180°
0.9 (V2)
180°
Max. leaf length (mt)
Max. leaf weight (kg)
3.5
8000N (~800 Kg)
1,8
8000N (~800 Kg)
1,8
8000N (~800 Kg)
2,5
8000N (~800 Kg)
2,5
8000N (~800 Kg)
1,8
8000N (~800 Kg)
1,8
8000N (~800 Kg)
2,5
8000N (~800 Kg)
2,5
8000N (~800 Kg)
P:17
ENGLISH
Speed (degrees/sec.)
3,9°
5,4°
5,4°
5,4°
5,4°
17
SUB - Ver. 03 -