Air Inlet - Ferroli TERMO ORIONE PLUS Manual De Instalación, Uso Y Mantenimiento

Estufa de pellets
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Every installation must provide for an easily accessible technical space for periodical maintenance.
The stove is provided with 4 adjustable feet to facilitate positioning on not perfectly flat floors. To adjust the height, tilt
the stove slightly and turn the feet as required. The stove is supplied with the ambient sensor fixed through a
wrapper on the back of the stove; we recommend to remove the wrapper and to locate the sensor in the best
position possible as to improve the temperature registration in accordance with the ambient context and the length of
the cable. As for temperature registration done at a certain distance
thermostat/ambient programming clock-thermostat – see. par.4.8.
- The stove cannot be installed in bedrooms, bathrooms and in general in rooms where another heating unit is already
installed without an independent air inflow.
- With wooden floors, install a floor protection base in conformity with the current regulations.Suitable fire-prevention
devices should be arranged for any eventuality.
- Do not install the stove in places with an explosive atmosphere.

2.3 Air inlet

The stove air inlet pipe or intake is located at the back and is round and 50 mm in diameter.
A quantity of air at least equal to that necessary for combustion must flow in the room where the stove is installed;
therefore the combustion air necessary to ensure correct operation of the stove must be drawn:
from the room, provided there is a wall air inlet near the stove, communicating with the outside and of minimum
area 100 cm² suitably protected externally by a grille and positioned so as not to be accidentally obstructed;
or with direct connection to the outside with an appropriate pipe having a minimum internal diameter of 50 mm
and maximum length of 1.5 m, provided with antiwind protection at the end (down bend).
The air inflow can also be obtained from a room adjoining that of installation, provided the flow can occur freely
through permanent openings to the outside; the room must not be used as a garage, for storing combustible
materials or for activities with fire risk.
2.4 Fume exhaust
Fumes can be exhausted through a connection to a conventional flue.
- The installer must check the efficiency and state of the flue and its conformity with the local, national and European
regulations.
- Certified pipes and connections with adequate seals guaranteeing their tightness must be used.
- In case of fire, shut down the stove, promptly call the fire department, and avoid continual attempts to extinguish it.
Antiwind
grille
Flue
Flue connection
Inspection door on
flue
Wall air inlet
min. 100 cm²
T union with
inspection cap
Floor protection base
we reccomend to install the ambient
36
A = 200 mm
B = 200 mm
C = 1000 mm
D = 200 mm
TERMO ORIONE PLUS
Tabla de contenido
loading

Este manual también es adecuado para:

Lsanx00a

Tabla de contenido